Chilled Water VAV System  

The chilled water VAV system consists AHU with heating and cooling coils, outside air intake, dampers, and etc. The system serves three zones with VAV boxes with hot water reheat. 

Photo11.jpg

Chilled Water AHU

Air Side Economizer 

The system contains three dampers: outside , return , and exhaust dampers to control the amount of ventilation introduced to the system. if the outside air is suitable, the control activates the economizer so an appropriate amount of fresh will be introduced to produce free cooling. The control provides several control strategies to active the economizer. A new strategy can be added to the control. 

VAV System Control Strategy  

The system has the following major control loops: space control loops, supply air temperature SAT control loop, and duct static pressure control loop, and ventilation control loop. The SAT control is to maintain the SAT at its setpoint by modulating the cooling coil valve, heating coil valve, or outside/retune/discharge dampers. The duct static pressure control is to maintain the duct static pressure at its set point by modulating the fan speed. The zone air temperature is controlled by two cascaded control loops; the error between the space temperature and its setpoint determines the airflow rate setpoint in the first control loop, and the VAV box damper is modulated to maintain the airflow rate at its setpoint in the second loop.

​

The control set points can be reset through multiple build-in control strategy options but any future strategies can be added for testing.  

Photo2.jpg

The chilled water VAV system serves three zones. 

Zone

Return Duct and Fan 

The system is equipped with return air duct and fan to bring the air back form the zones to central chilled water AHU. The fan is controlled to maintain a slightly positive pressure in the zone.  

Photo4.jpg

Return Fan